Negative pressures in full-scale distribution system: field investigation, modelling, estimation of intrusion volumes and risk for public health

Abstract : Various investigations encompassing microbial characterization of external sources of contamination (soil and trenchwater surrounding water mains, flooded air-valve vaults), field pressure monitoring, and hydraulic and transient analyses were conducted in the same distribution system where two epidemiological studies showing an increase in gastrointestinal illness for people drinking tap water were conducted in the 1990's. Interesting results include the detection of microorganisms indicators of fecal contamination in all external sources investigated but at a higher frequency in the water from flooded air-valve vaults, and the recording of 18 negative pressure events in the distribution system during a 17-month monitoring period. Transient analysis of this large and complex distribution system was challenging and highlighted the need to consider field pressure data in the process.
Document type :
Journal articles
Complete list of metadatas

Cited literature [19 references]  Display  Hide  Download

https://hal-riip.archives-ouvertes.fr/pasteur-00819606
Contributor : Charles M. Dozois <>
Submitted on : Monday, October 7, 2019 - 1:58:44 PM
Last modification on : Friday, October 23, 2020 - 4:43:40 PM

File

Negative_pressures_in_full-sca...
Publication funded by an institution

Licence


Distributed under a Creative Commons Attribution 4.0 International License

Identifiers

Collections

Citation

Marie-Claude Besner, G. Ebacher, B. S. Jung, B. Karney, J. Lavoie, et al.. Negative pressures in full-scale distribution system: field investigation, modelling, estimation of intrusion volumes and risk for public health. Drinking Water Engineering and Science, Copernicus Publications, 2010, 3 (2), pp.101-106. ⟨10.5194/dwes-3-101-2010⟩. ⟨pasteur-00819606⟩

Share

Metrics

Record views

151

Files downloads

75